Table 102: Auto-cleaning parameters
Index Parameter Min Max Unit Default ID Description
P3.21.1.9
Cleaning
Deceleration Time
0.1 300.0 s 0.1 1722
The motor deceleration
time when the Auto-
cleaning is active.
Table 103: Jockey pump parameters
Index Parameter Min Max Unit Default ID Description
P3.21.2.1
Jockey Function 0 2 0 1674
0 = Not used
1 = PID sleep: the
jockey pump runs
continuously when PID
sleep is active.
2 = PID sleep (level):
the jockey pump starts
at predefined levels
when PID sleep is
active.
P3.21.2.2 Jockey Start Level 0.00 100.00 % 0.00 1675
The jockey pump starts
when PID Sleep is
active and the PID
feedback signal goes
below the level set in
this parameter.
NOTE!
This parameter is
used only if P3.21.2.1
= 2 PID sleep (level).
P3.21.2.3 Jockey Stop Level 0.00 100.00 % 0.00 1676
The jockey pump stops
when PID Sleep is
active and the PID
feedback signal goes
above the level set in
this parameter, or
when the PID
controller wakes up
from sleep mode.
NOTE!
This parameter is
used only if P3.21.2.1
= 2 PID sleep level.
VACON · 202 PARAMETERS MENU
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205