Table 91: Frost protection parameters
Index Parameter Min Max Unit Default ID Description
P3.13.10.1 Frost Protection 0 1 0 1704
0 = Disabled
1 = Enabled
P3.13.10.2 Temperature Signal 0 29 6 1705
0 = Temperature Input
1 (-50..200 C)
1 = Temperature Input
2 (-50..200 C)
2 = Temperature Input
3 (-50..200 C)
3 = Temperature Input
4 (-50..200 C)
4 = Temperature Input
5 (-50..200 C)
5 = Temperature Input
6 (-50..200)
6 = Analogue input 1
7 = Analogue input 2
8 = Analogue input 3
9 = Analogue input 4
10 = Analogue input 5
11 = Analogue input 6
12 = ProcessDataIn1
(0-100%)
13 = ProcessDataIn2
(0-100%)
14 = ProcessDataIn3
(0-100%)
15 = ProcessDataIn4
(0-100%)
16 = ProcessDataIn5
(0-100%)
17 = ProcessDataIn6
(0-100%)
18 = ProcessDataIn7
(0-100%)
19 = ProcessDataIn8
(0-100%)
20 = Block Out.1
21 = Block Out.2
22 = Block Out.3
23 = Block Out.4
24 = Block Out.5
25 = Block Out.6
26 = Block Out.7
27 = Block Out.8
28 = Block Out.9
29 = Block Out.10
P3.13.10.3
Temperature Signal
Minimum
-100.0
P3.13.10.
4
°C/°F -50.0 (°C) 1706
The temperature value
that agrees to the
minimum value of the
set temperature signal.