Table 90: Input pressure supervision parameters
Index Parameter Min Max Unit Default ID Description
P3.13.9.4
Supervision Unit
Decimals
0 4 2 1688
The selection of the
quantity of decimals.
P3.13.9.5
Supervision Unit
Minimum Value
Varies Varies Varies Varies 1689
The signal value
minimum agrees to, for
example, 4mA, and the
signal value maximum
agrees to 20mA. The
values are scaled
linearly between these
2.
P3.13.9.6
Supervision Unit
Maximum Value
Varies Varies Varies Varies 1690
P3.13.9.7
Supervision Alarm
Level
Varies Varies Varies Varies 1691
An alarm shows (fault
ID 1363) if the
supervision signal
stays below the alarm
level longer than the
time set in P3.13.9.9.
P3.13.9.8
Supervision Fault
Level
Varies Varies Varies Varies 1692
A fault shows (fault ID
1409) if the supervision
signal stays below the
fault level longer than
the time set in
P3.13.9.9.
P3.13.9.9
Supervision Fault
Delay
0.00 60.00 s 5.00 1693
The delay time during
which to show the
supervision alarm or
fault.
P3.13.9.10
PID Setpoint
Reduction
0.0 100.0 % 10.0 1694
Gives the rate of the
setpoint reduction of
the PID controller
when the alarm for the
input pressure
supervision is active.
V3.13.9.11 Input Pressure Varies Varies Varies Varies 1695
The monitoring value
for the set signal of the
input pressure
supervision. Scaling
value as in P3.13.9.4.
PARAMETERS MENU VACON · 185