Table 38: Frequency reference parameters
Index Parameter Min Max Unit Default ID Description
P3.3.1.6
I/O Control
Reference B
Selection
0 9 4 * 131
Selection of the
reference source when
the control place is I/O
B. See above. You can
force the I/O B control
place to be active only
with a digital input
(P3.5.1.7).
P3.3.1.7
Keypad Control
Reference Selection
0 19 2 * 121
Selection of the
reference source when
the control place is
keypad.
0 = Preset Frequency 0
1 = Keypad
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID reference
7 = Motor
potentiometer
8 = Joystick
9 = Jogging reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
P3.3.1.8
Keypad Reference P3.3.1.1 P3.3.1.2. Hz 0.00 184
You can adjust the
frequency reference on
the keypad with this
parameter.
P3.3.1.9 Keypad Direction 0 1 0 123
The rotation direction
of the motor when the
control place is keypad.
0 = Forward
1 = Reverse
PARAMETERS MENU VACON · 125