EasyManua.ls Logo

Vacon 100 - Page 104

Vacon 100
342 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 23: Monitoring the temperature inputs
Index Monitoring value Unit Scale ID Description
V2.5.1
Temperature
input 1
°C 0.1 50
The measured value of temperature input 1.
The list of temperature inputs is made of the
first 6 available temperature inputs. The list
starts from slot A and ends in slot E. If an
input is available but no sensor is connected,
the list shows the maximum value because
the measured resistance is endless. To make
the value go to its minimum value, hardwire
the input.
V2.5.2
Temperature
input 2
°C 0.1 51
The measured value of temperature input 2.
See more above.
V2.5.3
Temperature
input 3
°C 0.1 52
The measured value of temperature input 3.
See more above.
V2.5.4
Temperature
input 4
°C 0.1 69
The measured value of temperature input 4.
See more above.
V2.5.5
Temperature
input 5
°C 0.1 70
The measured value of temperature input 5.
See more above.
V2.5.6
Temperature
input 6
°C 0.1 71
The measured value of temperature input 6.
See more above.
VACON · 104 MONITORING MENU
4
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon 100

Related product manuals