Index Parameter Min Max Unit Default ID Description
P3.1.2.1
Control Mode 0 2 0 600
0 = Frequency control
(open loop)
1 = Speed control
(open loop)
2 = Torque control
(open loop)
P3.1.2.2
Motor Type 0 1 0 650
0 = Induction motor
1 = PM motor
P3.1.2.3 Switching Frequency 1.5 Varies kHz Varies 601
If you increase the
switching frequency,
the capacity of the AC
drive reduces. To
reduce capacitive
currents in the motor
cable, when the cable
is long, we recommend
that you use a low
switching frequency.
To reduce the motor
noise, use a high
switching frequency.
P3.1.2.4
Identification 0 2 0 631
Identification
calculates or measures
the motor parameters
that are necessary for
a good control of the
motor and speed.
0 = No action
1 = At standstill
2 = With rotation
Before you do the
identification run, you
must set the motor
nameplate parameters
in the menu M3.1.1.