Table 34: Open loop settings
Index Parameter Min Max Unit Default ID Description
P3.1.4.7
Flying Start Options 0 63 0 1590
A checkbox
selection
B0 = Search the shaft
frequency only from
the same direction as
the frequency
reference
B1 = Disable AC
scanning
B4 = Use the frequency
reference for the initial
guess
B5 = Disable DC pulses
P3.1.4.8
Flying Start Scan
Current
0.0 100.0 % 45.0 1610
As a percentage of the
motor nominal current.
P3.1.4.9
Auto Torque Boost 0 1 0 109
0=Disabled
1=Enabled
P3.1.4.10
Torque Boost Motor
Gain
0.0 100.0 % 100.0 665
Scaling factor for the
motoring side IR-
compensation when
the torque boost is
used.
P3.1.4.11
Torque Boost
Generator Gain
0.0 100.0 % 0.0 667
Scaling factor for the
generating side IR-
compensation when
the torque boost is
used.
M3.1.4.12 I/f Start This menu includes 3 parameters. See the table below.
PARAMETERS MENU VACON · 119