Index Parameter Min Max Unit Default ID Description
P3.5.3.2.1
Basic RO1 Function 0 59 2 * 11001
The function
selection for Basic
R01
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault
inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Thermistor fault
9 = Motor regulator
active
10 = Start signal active
11 = Keypad control
active
12 = I/O B control
activated
13 = Limit supervision
1
14 = Limit supervision
2
15 = Fire Mode active
16 = Jogging activated
17 = Preset speed
active
18 = Quick stop
activated
19 = PID in Sleep mode
20 = PID soft fill active
21 = PID feedback
supervision (limits)
22 = Ext. PID
supervision (limits)
23 = Input press.
alarm/fault
24 = Frost prot. alarm/
fault
25 = Motor 1 control
26 = Motor 2 control
27 = Motor 3 control
28 = Motor 4 control
PARAMETERS MENU VACON · 145