Table 58: Standard I/O board analogue output settings
Index Parameter Min Max Unit Default ID Description
P3.5.4.1.1
AO1 function 0 31 2 * 10050
17 = ProcessDataIn4
(0-100%)
18 = ProcessDataIn5
(0-100%)
19 = ProcessDataIn6
(0-100%)
20 = ProcessDataIn7
(0-100%)
21 = ProcessDataIn8
(0-100%)
22 = Block Out.1
(0-100%)
23 = Block Out.2
(0-100%)
24 = Block Out.3
(0-100%)
25 = Block Out.4
(0-100%)
26 = Block Out.5
(0-100%)
27 = Block Out.6
(0-100%)
28 = Block Out.7
(0-100%)
29 = Block Out.8
(0-100%)
30 = Block Out.9
(0-100%)
31 = Block Out.10
(0-100%)
P3.5.4.1.2
AO1 filter time 0.0 300.0 s 1.0 * 10051
The filter time of the
analogue output signal.
See P3.5.2.1.2.
0 = No filtering
P3.5.4.1.3 AO1 minimum 0 1 0 * 10052
0 = 0 mA / 0V
1 = 4 mA / 2V
Make the selection of
the signal type
(current/voltage) with
the dip switches. The
analogue output
scaling is different in
P3.5.4.1.4. See also
P3.5.2.1.3.
PARAMETERS MENU VACON · 149