Table 65: Motor stall protection settings
Index Parameter Min Max Unit Default ID Description
P3.9.3.1 Motor Stall Fault 0 3 0 709
0 = No action
1 = Alarm
2 = Fault (Stop
according to stop
mode)
3 = Fault (Stop by
coasting)
P3.9.3.2
Stall Current 0.00 5.2 A 3.7 710
For a stall state to
occur, the current
must be above this
limit.
P3.9.3.3
Stall Time Limit 1.00 120.00 s 15.00 711
This is the maximum
time for a stall state.
P3.9.3.4 Stall Frequency Limit 1.00 P3.3.1.2 Hz 25.00 712
For a stall state to
occur, the output
frequency must be
below this limit for a
certain time.
VACON · 158 PARAMETERS MENU
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205