Table 68: Temperature input fault 1 settings
Index Parameter Min Max Unit Default ID Description
P3.9.6.1
Temperature Signal
1
0 63 0 739
Selection of
signals to use for
alarm and fault
triggering.
B0 = Temperature
Signal 1
B1 = Temperature
Signal 2
B2 = Temperature
Signal 3
B3 = Temperature
Signal 4
B4 = Temperature
Signal 5
B5 = Temperature
Signal 6
The maximum value is
taken from the set
signals and used for
alarm and fault
triggering.
NOTE!
Only the 6 first
temperature inputs
are supported (the
boards from slot A to
slot E).
P3.9.6.2 Alarm Limit 1 -30.0 200.0 °C 120.0 741
The temperature limit
for an alarm.
NOTE!
Only the inputs that
are set with
parameter P3.9.6.1
are compared.
P3.9.6.3 Fault Limit 1 -30.0 200.0 °C 120.0 742
The temperature limit
for an alarm.
NOTE!
Only the inputs that
are set with
parameter P3.9.6.1
are compared.
PARAMETERS MENU VACON · 161