Table 3: M1 Quick Setup
Index Parameter Min Max Unit Default ID Description
1.18 Automatic Reset 0 1 0 731
0 = Disabled
1 = Enabled
1.19
Response to External
Fault
0 3 2 701
0 = No action
1 = Alarm
2 = Fault (Stop
according to stop
mode)
3 = Fault (Stop by
coasting)
1.20
Response to AI Low
Fault
0 5 0 700
0 = No action
1 = Alarm
2 = Alarm+preset fault
frequency (P3.9.1.13)
3 = Alarm + previous
frequency
4 = Fault (Stop
according to stop
mode)
5 = Fault (Stop by
coasting)
1.21
Remote Control
Place
0 1 0 172
The selection of the
remote control place
(start/stop).
0 = I/O control
1 = Fieldbus control
QUICK STARTUP GUIDE VACON · 19