2 In the Edit mode, the slot value DigIN SlotA is
underlined and blinks. If you have more digital
inputs available in your I/O, for example, because of
option boards in slots C, D or E, make a selection of
them.
STOP
READY I/O
Ext Fault Close
P3.5.1.11ID:405
Min:
Max:
DigIN SlotA.3
3 To activate the terminal 3, push the arrow button
Right again.
STOP
READY I/O
Ext Fault Close
P3.5.1.11ID:405
Min:
Max:
DigIN SlotA.3
4 To change the terminal to 6, push the arrow button
Up 3 times. Accept the change with the OK button.
STOP
READY I/O
Ext Fault Close
P3.5.1.11ID:405
Min:
Max:
DigIN SlotA.6
5 If the digital input DI6 was already used for some
other function, a message shows on the display.
Change one of these selections.
STOP
READY I/O
ID:
At least one digital input has
been selected to several
operations.
To prevent possible unwanted
operations, please check all
digital input selection parameters.
VACON · 256 PARAMETER DESCRIPTIONS