Table 6: M1 Quick Setup
Index Parameter Min Max Unit Default ID Description
1.22
I/O Control
Reference A
Selection
0 9 3 117
The selection of the
frequency reference
source when the
control place is I/O A.
0 = Preset Frequency 0
1 = Keypad Reference
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID Reference
7 = Motor
Potentiometer
8 = Joystick Reference
9 = Jogging Reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
The application that
you set with parameter
1.2 gives the default
value.
1.23
Keypad Control
Reference Selection
0 9 1 121
The selection of the
frequency reference
source when the
control place is keypad.
See P1.22.
1.24
Fieldbus Control
Reference Selection
0 9 2 122
The selection of the
frequency reference
source when the
control place is
fieldbus. See P1.22.
1.25 AI1 Signal Range 0 1 0 379
0= 0..10V / 0..20mA
1= 2..10V / 4..20mA
1.26 AI2 Signal Range 0 1 1 390
0= 0..10V / 0..20mA
1= 2..10V / 4..20mA
1.27 RO1 Function 0 51 2 1101 See P3.5.3.2.1
QUICK STARTUP GUIDE VACON · 27
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
1

Table of Contents

Other manuals for Vacon 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 and is the answer not in the manual?

Vacon 100 Specifications

General IconGeneral
Product typeAC Drive
Enclosure classIP20
EMC filterBuilt-in
Power0.25 kW - 5.5 kW
Cooling methodFan
Braking chopperOptional

Related product manuals