ID716
Trip area
Time
Underload time counter
Underload•
No underl.
Trip/warning
ID713
Fig. 60: The Underload time counter function
P3.9.5.1 QUICK STOP MODE (ID 1276)
P3.9.5.2 (P3.5.1.26) QUICK STOP ACTIVATION (ID 1213)
P3.9.5.3 QUICK STOP DECELERATION TIME (ID 1256)
P3.9.5.4 RESPONSE TO QUICK STOP FAULT (ID 744)
With the quick stop function, you can stop the drive in an unusual procedure from I/O or
Fieldbus in unusual conditions. When the quick stop function is active, you can make the
drive decelerate and stop. It is possible to program an alarm or fault to put a mark in the
fault history that there was a request for a quick stop.
CAUTION!
Do not use the quick stop function as an emergency stop. An emergency stop must
stop the power supply to the motor. The quick stop function does not do this.
VACON · 282 PARAMETER DESCRIPTIONS
9
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205