With flow
Position 2Position 1
Pressure
No flow
Pipe length
PT PT
Fig. 74: The position of the pressure sensor
P3.13.7.1 ENABLE COMPENSATION FOR SETPOINT 1 (ID 1189)
P3.13.7.2 SETPOINT 1 MAX COMPENSATION (ID 1190)
The sensor is put in position 1. The pressure in the pipe stays constant when there is no flow.
But with flow, the pressure decreases farther in the pipe. To compensate for this, lift the
setpoint as the flow increases. Then the output frequency makes an estimate of the flow, and
the setpoint increases linearly with the flow.
PARAMETER DESCRIPTIONS VACON · 295