Table 16: M1.35 Multi-purpose
Index Parameter Min Max Unit Default ID Description
1.35.1 Control Mode 0 2 0 600
0 = U/f Freq Control
open loop
1 = Speed control open
loop
2 = Torque Control
open loop
1.35.2 Auto Torque Boost 0 1 0 109
0 = Disabled
1 = Enabled
1.35.3 Acceleration Time 2 0.1 300.0 s 10.0 502
Defines the time that is
necessary for the
output frequency to
increase from zero
frequency to maximum
frequency.
1.35.4 Deceleration Time 2 0.1 300.0 s 10.0 503
Defines the time that is
necessary for the
output frequency to
decrease from
maximum frequency to
zero frequency.
1.35.5 Preset Frequency 1 P1.3 P1.4 Hz 5.0 105
Preset Frequency
selected by digital
input DI4.
1.35.6 U/f Ratio Select 0 2 0 108
Type of U/f curve
between zero
frequency and the field
weakening point.
0 = Linear
1 = Squared
2 = Programmable
1.35.7
Field Weakening
Point Frequency
8.00 P1.4 Hz Varies 602
The field weakening
point is the output
frequency at which the
output voltage reaches
the field weakening
point voltage
1.35.8
Voltage at Field
Weakening Point
10.00 200.00 % 100.00 603
Voltage at field
weakening point in %
of motor nominal
voltage