6
Set a value for P3.1.1.5 Motor Cos Phi (so that it
agrees with the nameplate of the motor)
Range: 0.30…1.00
7
Set a value for P3.3.1.1 Minimum Frequency
Reference
Range: 0.00 Hz…P3.3.1.2
8
Set a value for P3.3.1.2 Maximum Frequency
Reference
Range: P3.3.1.1…320.00 Hz
9 Set a value for P3.4.1.2 Acceleration Time 1 Range: 0.1…300.0 s
10 Set a value for P3.4.1.3 Deceleration Time 1 Range: 0.1…300.0 s
11
Make a selection of a control place (where you give
the start/stop commands)
I/O Terminal
Fieldbus
Keypad
12 Set a value for P3.13.1.4 Process Unit Selection More than 1 selection
If your selection is other than %, you see the next questions. If your selection is %, the wizard
goes directly to question 17.
13
Set a value for P3.13.1.5 Process Unit Min The range depends on the selection in
question 12.
14
Set a value for P3.13.1.6 Process Unit Max The range depends on the selection in
question 12.
15 Set a value for P3.13.1.7 Process Unit Decimals Range: 0…4
16
Set a value for P3.13.3.3 Feedback 1 Source
Selection
See the table Feedback settings in Chapter
5.13 Group 3.13: PID controller
If you make a selection of an analogue input signal, you see the question 18. With other
selections, the wizard goes to question 19.
17
Set the signal range of the analogue input
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
18
Set a value for P3.13.1.8 Error Inversion
0 = Normal
1 = Inverted
19
Set a value for P3.13.2.6 Setpoint Source Selection See table Setpoints in Chapter 5.13 Group
3.13: PID controller
If you make a selection of an analogue input signal, you see the question 21. With other
selections, the wizard goes to question 23.
If you set Keypad Setpoint 1 or Keypad Setpoint 2 for the value, the wizard goes directly to
question 22.
WIZARDS VACON · 67