7-23
Alarm Configuration
PlugThresholds: Defines current consumption level(s) that will trigger alarm(s) at
each switched outlet. The Plug Thresholds can be configured to trigger an alarm
when current consumption rises above a user-defined "High" value and/or when
current consumption falls below a user-defined "Low" value. This allows you to
define a "normal" current range for each outlet, allowing the Plug Current Alarm to
be triggered whenever current consumption strays outside of this range.
(Default = undefined)
PlugGroupThresholds: Defines current consumption level(s) that will trigger
alarm(s) for each user-defined Plug Group. The Plug Group Thresholds can be
configured to trigger an alarm when total current consumption for a given Plug
Group rises above a user-defined "High" value and/or when current consumption
falls below a user-defined "Low" value. This allows you to define a "normal" current
range for each Plug Group, allowing the Plug Current Alarm to be triggered
whenever total current consumption for the Plug Group strays outside of this range.
(Default = undefined)
Note:InordertodefinePlugGroupThresholds,youmustfirstdefineatleast
onePlugGroupasdescribedinSection5.6.
Plug"Off"LowAlarm: Allows you to configure the "Low" current alarm to suppress
triggering when an outlet is purposely switched Off. When this feature is "On",
the RSM-8R8-CM will generate a Low alarm whenever current drops below the
Low threshold value, even if the current drop is due to an outlet being purposely
switched Off. When this feature is "Off", the RSM-8R8-CM will not generate a Low
alarm due to a current drop caused by an outlet being switched Off. (Default = On)
Notes:
• ThePlug"Off"LowAlarmfeaturewillalsobeappliedtoPlugGroups.
• WhenthePlug"Off"LowAlarmfeatureisenabled(On),theRSM-8R8-CM
willalwaysgenerateaLowcurrentalarmwhencurrentdropsbelowtheLow
thresholdvalue,evenwhenthecurrentdropwascausedbyoneormore
outletsinthePlugGroupbeingpurposelyswitchedOff.
• WhenthePlug"Off"LowAlarmfeatureisdisabled(Off),theRSM-8R8-CM
willnotgenerateaLowcurrentAlarmwhenacurrentdropiscausedbyall
outletsinthePlugGroupbeingpurposelyswitchedOff.
ResendDelay: Determines how long the RSM-8R8-CM will wait to resend an email
message generated by this alarm, when the initial attempt to send the notification
was unsuccessful. (Default = 60 Minutes)
NotifyUponClear: When this item is enabled, the RSM-8R8-CM will send
additional notification when the situation that caused the alarm has been corrected.
For example, when Notify Upon Clear is enabled, the RSM-8R8-CM will send initial
notification when it detects that a current consumption has risen above the defined
"High" trigger value, and then send a second notification when it determines that
current consumption has fallen below the "Low" trigger value. (Default = On)