5 Specifications and Dimensional Drawings of Cables and Peripheral Devices
5.8.9 Molded-case Circuit Breaker (MCCB)
5-74
(2) Specifications
(3) Precautions
Circuit Breakers
Select a breaker for inverters.
High-frequency current leaks from the servomotor armature because of switching operations inside the SER-
VOPACK.
(a) Maximum Input Current
• The instantaneous maximum output of SERVOPACK is approximately 3 times of the rated output for
maximum 3 seconds. Accordingly, select a circuit breaker whose operating time is 5 seconds or more at
300% of SERVOPACK rated current.
The general-purpose and low-speed acting molded-case circuit breakers are applicable.
• The power supply capacity per SERVOPACK when using a servomotor is described in 2.6.2 Molded-case
Circuit Breaker and Fuse Capacity. Select a circuit breaker with the capacity larger than the effective
load current (when using multiple SERVOPACKs) calculated from the total power supply capacity.
• The power consumption of other controllers must be considered when selecting a circuit breaker.
(b) Inrush Current
• Refer to 2.6.2 Molded-case Circuit Breaker and Fuse Capacity for SERVOPACK inrush current.
• The allowable inrush current for a low-speed acting circuit breaker is approximately 10 times of the rated
current for 0.02 seconds.
• When turning ON multiple SERVOPACKs simultaneously, select a molded-case circuit breaker with the
allowable current for 20 ms larger than the total inrush current shown in 2.6.2 Molded-case Circuit
Breaker and Fuse Capacity.
Phase 3φ3W
Number of Poles 3
Rated Voltage Common for 100 V/200 V/415 VAC
Rated Current and
Motor Rated Capacity under
Basic Ambient Temperature of 40°C
(104 °F)
Rated
Current
A
kW Rated
Current
A
kW
200 V 415 V 200 V 415 V
45
11 22
(8)
-3.7
(40)
- 18.5
7.1
1.5 -
32
7.5 15
(5)
-2.2
25
5.5 11
4
0.75 1.5
16
3.7 7.5
2.5
0.4 -
(12)
-5.5
(2)
-0.75
10
2.2 -
1.4
0.2 -
Rated Current Sensitivity 30 mA, 100 (200 or 500 switchable)
Operating Time Within 0.1 s
Ground Fault Display Method Mechanical button
Rated Interrupt-
ing Current
JIS C8371
415 VAC 2.5 kA
200 VAC 5 kA
100 VAC 5 kA
IMPORTANT