2.6 Selecting Peripheral Devices
2-31
2
Note: 1. If some SERVOPACKs are wired at the same time, select the proper magnetic contactors accord-
ing to the total capacity.
2. The following table shows the manufacturers of each device.
2.6.4 Regenerative Resistors and Brake Power Supply Units
Peripheral Device Manufacturer
Noise Filter
FN, FS type: Schaffner Electronic
FMAC type: Timonta AG
Magnetic Contactor Yaskawa Controls Co., Ltd.
Surge Suppressor Yaskawa Controls Co., Ltd.
DC Reactor Yaskawa Controls Co., Ltd.
Main Circuit
Power Supply
SERVOPACK Model
Regenerative Resistor
(Refer to 5.8.6, 5.8.7, and 6.5.)
Brake Power Supply
Unit
(Refer to 5.8.5.)
Capacity
(kW)
SGDH-
Built-in
Externally
connected
Resistance
(Ω)
Capacity
(W)
Single-phase
100 V
0.03 A3BE
−−
−
24 VDC brake (provided
by a customer)
∗
5
90 VDC brake
• LPDE-1H01
for 100 VAC input
• LPSE-2H01
for 200 VAC input
0.05 A5BE
0.10 01BE
0.20 02BE
Single-phase
200 V
0.03 A3AE
0.05 A5AE
0.10 01AE
0.20 02AE
0.40 04AE
Single-phase
220 V
0.75 08AE-S 50 60
1.50 15AE-S 25 140 −
Three-phase
200 V
0.45 05AE
50 60
−
0.75 08AE
1.0 10AE
1.5 15AE 30 70
2.0 20AE 25 140
3.0 30AE 12.5 140
5.0 50AE 8 280
6.0 60AE
(6.25
)
∗
1
(880)
∗
1
JUSP-RA04
7.5 75AE
(3.13)
∗
2
(1760)
∗
2
JUSP-RA0511.0 1AAE
15.0 1EAE
Three-phase
400 V
0.45 05DE
108 70
−
1.0 10DE
1.5 15DE
2.0 20DE
45 140
3.0 30DE
5.0 50DE 32 180
6.0 60DE
(18)
∗
3
(880)
∗
3
JUSP-RA18
7.5 75DE
11.0 1ADE
(14.25)
∗
4
(1760)
∗
4
JUSP-RA19
15.0 1EDE