6.5 Connecting Regenerative Resistors
6-37
6
(c) SERVOPACK’s with Capacities of 6.0 kW or More
No built-in regenerative resistor is provided, so the external regenerative resistor is required. The special
regenerative resistor units are as follow:
The following diagram shows the connection method between the SERVOPACK and the regenerative resis-
tor unit.
Note: Connect a regenerative resistor unit between B1 and B2 terminals. The regenerative resis-
tor unit is provided by the customer.
Main Circuit
Power Supply
Applicable
SERVOPACK
Model SGDH-
Applicable
Regenerative
Resistor Unit
Resis-
tance
()
Specifications
Three-phase
200 V
60AE JUSP-RA04
6.25
25
220 W
×
4 (parallel connection)
75AE to -1EAE JUSP-RA05
3.13
25
220 W
×
8 (parallel connection)
Three-phase
400 V
60DE, -75DE JUSP-RA18
18
18
220 W
×
4 (direct/parallel connection)
1ADE, -1EDE JUSP-RA19
14.25
28.5
220 W
×
8 (direct/parallel connection)
L1 L2 L3
UB2B1+ VW
WARNING
MODE/SET
DATA/
Ve r.
POWER
BATTERY
CHARGE
SGDH-
SERVOPARK 200V
YASKAWA
Regenerative Resistor Unit
JUSP-RA
SERVOPACK