CALL #Ceiling lamp
ON :=M20.0
OFF :=20.1
ONOFF :=20.2
Duration :=T#5M
Output :=M20.3
PulseOn :=
PulseOff :=
CALL #Blind
Up :=M30.0
Down :=M30.1
CentralUp :=
CentralDown :=
TimeMaxDuration :=T#10S
TimePause :=T#1S
TimeShortLong :=T#2S
Endable :=
BlindUp :=M30.6
BlindDown :=M30.7
7.2 Room
7.2.1 FB 45 - LAMP - Controlling lamp / socket
With this block you can control load relays for lamps and sockets. It can be controlled via
On/Off button or via separate On and Off button. Additionally with Duration you have the
possibility to set a duration for the automatic switching-off. With TimeDebounce you can
specify a debounce time for the input signals.
n When driving a monostable relay the output remains set as long as the relay is to be
activated. With an edge change 0-1 at OnOff respectively On the static output Output
is set. It remains set until you reset it with an edge change 0-1 at OnOff respectively
Off or the time of Duration has expired.
n When controlling a bistable relay 2 outputs are used. Here PulseOn controls the
switch on and PulseOff the switch off procedure. With TimePulse the pulse duration
and with TimePause the switch time of the two outputs can be specified.
Parameters
Parameter Declaration Data type Description
OnOff INPUT BOOL With an edge change 0-1 Output is activated
respectively deactivated and PulseOn or Pul-
seOff is activated.
Default: FALSE
On INPUT BOOL With an edge change 0-1 Output is activated
respectively deactivated and PulseOn is acti-
vated.
Default: FALSE
Off INPUT BOOL With an edge change 0-1 Output is deactivated
and PulseOff is activated.
Default: FALSE
Network 1
Network 2
Description
VIPA SPEED7
Building Control
Room > FB 45 - LAMP - Controlling lamp / socket
HB00 | OPL_SP7 | Operation list | en | 18-30 103