OB83_EV_CLASS OB83_FLT_ID Description
39h 51h PROFINET IO module removed
54h PROFINET IO submodule removed
38h 54h PROFINET IO submodule inserted and matches configured submodule
55h PROFINET IO submodule inserted, but does not match configured sub-
module
56h PROFINET IO submodule inserted, but error with module parameters
58h PROFINET IO submodule, access error corrected
39h 61h Module removed or not responding OB83_MDL_TYPE: Actual module
type
38h 61h Module inserted. Module type OK OB83_MDL_TYPE: Actual module
type
63h Module inserted but incorrect module type OB83_MDL_TYPE: Actual
module type
64h Module inserted but problem (module ID cannot be read)
OB83_MDL_TYPE: Configured module type
65h Module inserted but error in module parameter assignment
OB83_MDL_TYPE: Actual module type
39h 66h Module not responding, load voltage error
38h 66h Module responds again, load voltage error corrected
33h 67h Start of module reconfiguration
32h 67h End of module reconfiguration
39h 68h Module reconfiguration terminated with error
If you are using a DP-V1- or PROFINET-capable CPU you can obtain
additional information on the interrupt with the help of SFB 54 "RALRM"
which exceeds the start information of the OB.
6.9.5 OB 85 - OBNL_FLT - Priority Class Error
The operating system of the CPU calls OB 85 whenever one of the following events
occurs:
n Start event for an OB that has not been loaded
n Error when the operating system accesses a block
n I/O access error during update of the process image by the system (if the OB 85 call
was not suppressed due to the configuration)
The OB 85 may be delayed by means of the SFC 41 and re-enabled by the SFC 42.
If OB 85 has not been programmed, the CPU changes to STOP mode
when one of these events is detected.
Description
VIPA SPEED7
Organization Blocks
Asynchronous error Interrupts > OB 85 - OBNL_FLT - Priority Class Error
HB00 | OPL_SP7 | Operation list | en | 18-30 92