Bit Assignment Description
0 /FC First check bit
1 RLO Result of (previous) logic instruction
2 STA Status
3 OR Or
4 OS Stored overflow
5 OV Overflow
6 CC0 Condition code
7 CC1 Condition code
8 BR Binary result
9 ... 15 not used -
3.6 Addressing examples
Addressing example Description
Immediate addressing
L +27 Load 16bit integer constant "27" in ACCU1
L L#-1 Load 32bit integer constant "-1" in ACCU1
L 2#1010101010101010 Load binary constant in ACCU1
L DW#16#A0F0_BCFD Load hexadecimal constant in ACCU1.
L "End" Load ASCII code in ACCU1
L T#500ms Load time value in ACCU1
L C#100 Load time value in ACCU1
L B#(100,12) Load constant as 2byte
L B#(100,12,50,8) Load constant as 4byte
L P#10.0 Load area-internal pointer in ACCU1
L P#E20.6 Load area-crossing pointer in ACCU1
L -2.5 Load real number in ACCU1
L D#1995-01-20 Load date
L TOD#13:20:33.125 Load time-of-day
Direct addressing
A I 0.0 AND operation of input bit 0.0
L IB 1 Load input byte 1 in ACCU1
L IW 0 Load input word 0 in ACCU1
L ID 0 Load input double word 0 in ACCU1
Indirect addressing timer/counter
SP T [LW 8] Start timer; timer no. is in local data word 8
VIPA SPEED7
IL operations
Addressing examples
HB00 | OPL_SP7 | Operation list | en | 18-30 28