EasyManua.ls Logo

YASKAWA VIPA SPEED7 - Module Diagnostic Information Via Logical Address - SSL-ID: 00 B3 H

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17.23 Module diagnostic information via logical address - SSL-ID: 00B3h
If you read this partial list, you obtain all the diagnostic data of a module. You can also
obtain this information for PROFIBUS DP and submodules. The diagnostic record 1 con-
tains the 4 bytes of diagnostic data that are also in data record 0, plus module-specific
diagnostics data that describe the state of a channel or a channel group. The module is to
be specified via the logical base address.
Content Value Description
SSL_ID 00B3h Shows all the diagnostic data of a module.
INDEX xxxxh Here the following is to be specified via INDEX:
n Bit 0 ... 14: Logical base address of the module
n Bit 15:
0: Input
1: Output
LENTHDR xxxxh The length of the record set depends on the module.
N_DR 0001h Number of record set (1)
Information to length and structure of the diagnostic data may be found in
the corresponding manual of your diagnosable module.
Description
Header