FIFO Ring buffer max. 250 telegrams 1024byte
CONTROL Software handshake via CONTROL block
For recognizing a signal change a minimum pulse time is necessary. The
decisive factors are CPU cycle time, the refresh time on the CP and the
response time of the communication partner.
10.2.2 FB 60 - SEND - Send to System SLIO CP 040
This FB serves for the data output from the CPU to the System SLIO CP 040. Here you
define the send range via the identifiers DB_NO, DBB_NO and LEN. A rising edge at
REQ a transmission is initiated and the data is sent.
Parameters
Name Declaration Type Description
REQ IN BOOL Release SEND with positive edge.
R IN BOOL Release synchronous reset.
LADDR /
HW_ID
IN INT /
HW_IO
n LADDR
– Logical base address of the CP.
– When used in CPUs from VIPA or S7-300 CPUs from Siemens.
n HW_ID
– HW identifier to address the CP.
– When used in S7-1500 CPUs from Siemens.
DB_NO IN INT Number of DB containing data to send.
DBB_NO IN INT Data byte number - send data starting from data byte.
LEN IN INT Length of telegram in byte, to be sent.
IO_SIZE IN WORD Configured IO size of the module.
DONE* OUT BOOL Send order finished without errors.
ERROR* OUT BOOL Send order finished with errors.
Parameter STATUS contains the error information.
STATUS* OUT WORD Specification of the error with ERROR = 1.
Description
VIPA SPEED7
Serial Communication
CP040 > FB 60 - SEND - Send to System SLIO CP 040
HB00 | OPL_SP7 | Operation list | en | 18-30 220