EasyManua.ls Logo

YASKAWA VIPA SPEED7 - SFB 33 - ALARM - Messages with Acknowledgement Display

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ERR_CODE
n When an error occurs the status of SFB 32 remains at the current value and output
ERR_CODE contains one of the following error codes:
ERR_CODE Description
0000h No error has occurred
8081h illegal value for LST_STEP
8082h illegal value for DSC
8083h illegal value for DSP
8084h The product DCC = DTBP x S_PRESET [DSC] exceeds the value
2
31-1
(appr. 24.86 days)
14.2.13 SFB 33 - ALARM - Messages with acknowledgement display
Generating block-related messages with acknowledgement display:
n SFB 33 ALARM monitors a signal:
Acknowledgement triggered reporting is disabled (default): The block generates a
message both on a rising edge (event entering state) and on a falling edge (event
leaving state) to which associated values can be added.
Acknowledgement triggered reporting is enabled: After an incoming message is
generated for the signal, the block will no longer generate messages until you
have acknowledged this incoming message on a displaying device.
n When the SFB is first called, a message with the current signal state is sent. The
message is sent to all stations logged on for this purpose.
n Once your acknowledgement has been received from a logged on display device, the
acknowledgement information is passed on to all other stations logged on for this pur-
pose.
n One message memory with 2 memory blocks is available for each instance of SFB 33
ALARM.
n SFB 33 ALARM complies with the IEC 1131-5 standard.
Parameter Declaration Data type Memory block Description
EN_R INPUT BOOL I, Q, M, D, L Control parameter
SIG INPUT BOOL I, Q, M, D, L The signal to be monitored.
ID INPUT WORD Constant
(I, Q, M, D, L)
Data channel for messages: EEEEh.
ID is only evaluated at the first call.
EV_ID INPUT DWORD Constant
(I, Q, M, D, L)
Message number (not allowed: 0)
SEVERITY INPUT WORD Constant
(I, Q, M, D, L)
Weighting of the event
DONE OUTPUT BOOL I, Q, M, D, L Status parameter DONE:
Message generation completed.
ERROR OUTPUT BOOL I, Q, M, D, L ERROR status parameter
Error information
Description
Parameter
VIPA SPEED7
Integrated Standard
System Function Blocks > SFB 33 - ALARM - Messages with acknowledgement display
HB00 | OPL_SP7 | Operation list | en | 18-30 752

Table of Contents