Codes that are returned by RETVAL:
Code Description
0000h OK, file has been deleted
7000h REQ = 0, BUSY = 0 (nothing present)
7001h REQ = 1, 1. call
7002h Block is executed
8010h Parameter FILENAME is not available (e.g. DB not loaded)
8011h FILENAME is defective
(e.g. is not conform with 8.3 format or special character)
A000h System internal error occurred
A001h The defined MEDIA type is not valid
A002h The file is write-protected
A004h File FILENAME is not found
A005h FILENAME is a directory - you cannot delete
A006h File is just open
A007h Memory card is write-protected
A100h General file system error (e.g. no memory card plugged)
16.4 System Functions
16.4.1 SFC 75 - SET_ADDR - Set PROFIBUS MAC address
With this SFC you can change the MAC address of the integrated PROFIBUS interface of
a CPU. The function is only possible in the passive DP slave mode. To identify the diag-
nostic address is used. The SFC is asynchronous and can be applied only to one inter-
face. At STOP and subsequent warm start the set network address is retained. With Pow-
erOFF-PowerON or on overall reset the interface gets the configured node number The
DP slave consistently assumes the identity of the DP slave with the new address. For the
DP master the DP slave with the old address fails and a DP slave with the new address
returns. If an address is selected, which is already used by another node on the DP line,
then both slaves fail in accordance to the DP communication.
Parameters
Parameter Declaration Data type Memory area Description
REQ INPUT BOOL I, Q, M, D, L Function request with REQ = 1
LADDR INPUT WORD I, Q, M, D, L Identification of the interface
ADDR INPUT BYTE I, Q, M, D, L New node address
RET_VAL OUTPUT INT I, Q, M, D, L Error code
BUSY OUTPUT BOOL I, Q, M, D, L BUSY = 1: In progress
RETVAL (Return value)
Description
VIPA SPEED7
System Blocks
System Functions > SFC 75 - SET_ADDR - Set PROFIBUS MAC address