7.2.3 FB 47 - DSTRIKE - Electric door opener
With this block an electric door opener can be controlled, if its not locked with DoorI-
sLocked.
n With an edge change 0-1 at the input Open for the duration ‘TimeOpening’ ‘Output’ is
controlled.
n With an edge change 0-1 at the input EnableAlwaysOpen respectively DisableAlway-
sOpen Open is static activated respectively deactivated. Additionally with set Enable-
AlwaysOpen the static output AlwaysOpen is set.
n You can connect your door contacts at DoorIsClosed and DoorIsLocked. DoorI-
sClosed is set, as soon as the door is closed. DoorIsLocked is set as soon as the
door is locked, i.e. the contact is controlled by the locking mechanism of the door and
opening of the door by means of the electric door opener is disabled.
Parameters
Parameter Declaration Data type Description
Open INPUT BOOL With an edge change 0-1 Output is activated for
the duration of TimeOpening.
Default: FALSE
EnableAlwaysOpen INPUT BOOL With an edge change 0-1 Output is static set.
Default: FALSE
DisableAlwaysOpen INPUT BOOL With an edge change 0-1 Output is static reset.
Default: FALSE
TimeOpening INPUT TIME Time for the duration of the activation of Output.
Default: 3s
DoorIsClosed INPUT BOOL
n Optional - Position door
TRUE: Door is closed
FALSE: Door is open
Default: FALSE
DoorIsLocked INPUT BOOL
n Optional - Lock state of the door
– TRUE: Door is locked
– FALSE: Door is not locked
Default: FALSE
Output OUTPUT BOOL Static output to drive a monostable relay.
AlwaysOpen OUTPUT BOOL Static output to indicate "Door is static open".
Description
VIPA SPEED7
Building Control
Room > FB 47 - DSTRIKE - Electric door opener
HB00 | OPL_SP7 | Operation list | en | 18-30 106