ERROR STATUS
(decimal)
Description
1 12 The call to the FB/SFB
n contains an instance DB that does not belong to the
FB/SFB 14
n contains a global DB instead of an instance DB
n could not locate an instance DB
(load a new instance DB from the PG)
1 20 Not enough memory.
The data are received consistently if you evaluate the current use of range RD_i com-
pletely before initiating another job.
14.2.10 FB/SFB 15 - PUT - Remote CPU write
The FB/SFB 15 PUT can be used to write data to a remote CPU. The respective CPU
may be in RUN mode or in STOP mode.
Please note that this block calls the FC or SFC 201 AG_PUT internally.
These must not be overwritten! The direct call of an internal block leads
to errors in the corresponding instance DB!
Depending upon communication function the following behavior is present:
n Siemens S7-300 Communication (FB 15)
– The data is sent on a rising edge at REQ. The parameters ID, ADDR_1 and SD_1
are transferred on each rising edge at REQ. After a job has been completed, you
can assign new values to the ID, ADDR_1 and SD_1 parameters.
n Siemens S7-400 Communication (SFB 15)
– The SFB is started on a rising edge at REQ. In the process the pointers to the
areas to be written (ADDR_i) and the data (SD_i) are sent to the partner CPU.
Parameters
Parameter Declaration Data type Memory block Description
REQ INPUT BOOL I, Q, M, D, L control parameter request, a rising edge activates
the data exchange
(with respect to the most recent FB/SFB-call)
ID INPUT WORD I, Q, M, D,
constant
A reference for the connection. Format W#16#xxxx
DONE OUTPUT BOOL I, Q, M, D, L Status parameter DONE: function completed.
Data consistency
Description
VIPA SPEED7
Integrated Standard
System Function Blocks > FB/SFB 15 - PUT - Remote CPU write