EasyManua.ls Logo

YASKAWA VIPA SPEED7 - Transfer Instructions

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.15 Transfer instructions
Transfer the contents of ACCU1 into the addressed operand.
The status word is not affected.
Com-
mand
Operand Parameter Function Length
in words
T Transfer the contents of ACCU1-LL to ...
IB a
QB a
PQB a
MB a
LB a
DBB a
DIB a
0.0 ... 2047
0.0 ... 2047
0.0 ... 8191
0.0 ... 8191
parameterizable
0.0 ... 65535
0.0 ... 65535
input byte
output byte
periphery output byte
bit memory byte
local data byte
data byte
instance data byte
1/2
1/2
1/2
1/2
2
2
2
g [AR1,m]
g [AR2,m]
B [AR1,m]
B [AR2,m]
Parameter
register-indirect, area-internal (AR1)
register-indirect, area-internal (AR2)
area-crossing (AR1)
area-crossing (AR2)
via parameters
2
2
2
2
2
T Transfer the contents of ACCU1-L to ...
IW
QW
PQW
MW
LW
DBW
DIW
0.0 ... 2046
0.0 ... 2046
0.0 ... 8190
0.0 ... 8190
parameterizable
0.0 ... 65534
0.0 ... 65534
input word
output word
periphery output word
bit memory word
local data word
data word
instance data word
1/2
1/2
1/2
1/2
2
2
2
h [AR1,m]
h [AR2,m]
W [AR1,m]
W [AR2,m]
Parameter
register-indirect, area-internal (AR1)
register-indirect, area-internal (AR2)
area-crossing (AR1)
area-crossing (AR2)
via parameters
2
2
2
2
2
T Transfer the contents of ACCU1 to ...
Transfer instructions
VIPA SPEED7
IL operations
Transfer instructions
HB00 | OPL_SP7 | Operation list | en | 18-30 47

Table of Contents

Related product manuals