The following codes can be returned:
Code Description
0x0000 No error
0x80D0 Channel 0 not in status active
0x80D1 Channel 1 not in status active
0x80D6 Channel 0: Input value RESOLUTION_CH0 = 0
0x80D7 Channel 1: Input value RESOLUTION_CH1 = 0
0x80D8 Channel 0: Input value RESOLUTION_CH0 < 0
0x80D9 Channel 1: Input value RESOLUTION_CH1 < 0
0x80DA Channel 0: Measured time value = 0
0x80DB Channel 1: Measured time value = 0
0x80DC Channel 0: Measured time value < 0
0x80DD Channel 1: Measured time value < 0
0x80DE Channel 0: Measured time value > 0x7FFFFFF
0x80DF Channel 1: Measured time value > 0x7FFFFFF
0x80E2 Channel 0: Determined number of edges < 0
0x80E3 Channel 1: Determined number of edges < 0
0x80E4 Channel 0: Determined number of edges > 0xFFFFFF
0x80E5 Channel 1: Determined number of edges > 0xFFFFFF
0x80E6 Channel 0: Determined rotational speed > max. (DINT)
0x80E7 Channel 1: Determined rotational speed > max. (DINT)
0x80E8 Channel 0: No valid measurement within the entered measurement period
0x80E9 Channel 1: No valid measurement within the entered measurement period
12.2 Energy Measurement
12.2.1 Overview
12.2.1.1 Terms
A measurand is a physical quantity that can be measured such as current, voltage or
temperature.
A measured value is a value of a measurand, which is determined by measurement or by
calculation.
In the module each measurand one ID is assigned. The access to the measured value of
a measurand happens by means of the corresponding ID.
ERROR (Return value)
Measurand
Measured value
ID
VIPA SPEED7
Device Specific
Energy Measurement > Overview
HB00 | OPL_SP7 | Operation list | en | 18-30 264