17.21 Module diagnostic information - SSL-ID: 00B1h
If you read this partial list, you obtain the first 4 diagnostic bytes of a module with diag-
nostic capability.
Content Value Description
SSL_ID 00B1h Shows the first 4 diagnostic bytes of a module.
INDEX xxxxh Here the following is to be specified via INDEX:
n Bit 0 ... 14: Logical base address of the module
n Bit 15:
0: Input
1: Output
LENTHDR 0004h A record set is 2words long (4bytes).
N_DR 0001h Number of record set (1)
Record set SSL_ID: 00B1h
INDEX
offset
Length Description
0 1byte
n Bit 0: Module fault (group fault ID)
n Bit 1: Internal fault
n Bit 2: External fault
n Bit 3: Channel error exists
n Bit 4: No external auxiliary voltage
n Bit 5: No front connector
n Bit 6: Module not assigned parameters
n Bit 7: Wrong parameters on module
1 1byte
n Bit 0 ... 3: Module class
0000: CPU
0101: Analog modules
1000: FM
1100: CP
1111: Digital modules
0011: DP Norm slave
0100: IM
n Bit 4: Channel information exists
n Bit 5: User information exists
n Bit 6: Diagnostic interrupt from substitute
n Bit 7: Maintenance requirement (PROFINET IO only)
Description
Header
VIPA SPEED7
SSL System status list
Module diagnostic information - SSL-ID: 00B1h
HB00 | OPL_SP7 | Operation list | en | 18-30 988