EasyManua.ls Logo

YASKAWA VIPA SPEED7 - SFC 71 - LOG_GEO - Determining the Slot Belonging to a Logical Address

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RET_VAL (Return value)
Value Description
0000h The job was executed without errors.
8094h No subnet was configured with the specified SUBNETID.
8095h Invalid value for STATION parameter
8096h Invalid value for SLOT parameter
8097h Invalid value for SUBSLOT parameter
8099h The slot is not configured.
809Ah The interface module address is not configured for the selected slot.
8xyyh General error information
Ä
Chap. 4.2 ‘General and Specific Error Information RET_VAL’ page 66
14.1.55 SFC 71 - LOG_GEO - Determining the slot belonging to a logical address
SFC 71 LOG_GEO (convert logical address to geographical address) lets you determine
the module slot belonging to a logical address as well as the offset in the user data area
of the module.
Description
VIPA SPEED7
Integrated Standard
System Functions > SFC 71 - LOG_GEO - Determining the slot belonging to a logical address
HB00 | OPL_SP7 | Operation list | en | 18-30 717