EasyManua.ls Logo

YASKAWA VIPA SPEED7 - SFC 70 - GEO_LOG - Determining the Start Address of a Module

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Value Description
80C2h Temporary lack of resources for the communication partner, e.g.:
n The communication partner is currently processing the maximum number of operations
n The required resources (memory, etc.) are already occupied.
n Not enough memory (initiate compression).
80C3h Error when establishing a connection, e.g.:
n The local station is connected to the MPI sub-net.
n You have addressed the local station on the MPI sub-net.
n The communication partner cannot be contacted any longer.
n Temporary lack of resources for the communication partner.
14.1.54 SFC 70 - GEO_LOG - Determining the Start Address of a Module
Assumption: the associated module slot of the module is known from the channel of a
signal module. With SFC 70 GEO_LOG (convert geographical address to logical
address) you can determine the associated start address of the module, that is, the
smallest I address or Q address. If you use SFC 70 on power modules or modules with
packed addresses, the diagnostic address is returned.
Parameters
Parameter Declaration Data Type Memory Area Description
MASTER INPUT INT I, Q, M, D, L,
constant
Area ID:
n 0, if the slot is located in one of
the racks 0-3 (S7-300) or 0 bis 21
(S7-400)
n 1 to 32: DP master system ID of
the associated field device if the
slot is located in a field device on
PROFIBUS
n 100 to 115: PROFINET IO
system ID of the associated field
device if the slot is located in a
field device on PROFINET
STATION INPUT INT I, Q, M, D, L,
constant
n No. of rack, if area ID= 0
n Station number of field device if
area ID > 0
SLOT INPUT INT I, Q, M, D, L,
constant
Slot no.
SUBSLOT INPUT INT I, Q, M, D, L,
constant
Interface module slot (if no interface
module can be inserted, enter 0 here)
RET_VAL OUTPUT INT I, Q, M, D, L Error information
LADDR OUTPUT WORD I, Q, M, D, L Start address of the module Bit 15 of
LADDR indicates whether an input
address (bit 15 = 0) or an output
address (bit 15 = 1) is present
Description
VIPA SPEED7
Integrated Standard
System Functions > SFC 70 - GEO_LOG - Determining the Start Address of a Module
HB00 | OPL_SP7 | Operation list | en | 18-30 716