DONE
(SEND)
NDR
(RECV)
ERROR STATUS Description
0 0 1 8091h Module start address not within double word grid.
0 0 1 8092h ANY reference contains type setting unequal BYTE.
- 0 1 80A0h Negative acknowledgement at reading from module.
0 0 1 80A4h reserved
0 0 1 80B0h Module doesn’t recognize the record set.
0 0 1 80B1h The length setting (in parameter LEN) is invalid.
0 0 1 80B2h reserved
0 0 1 80C0h Record set not readable.
0 0 1 80C1h The set record set is still in process.
0 0 1 80C2h There is a job jam.
0 0 1 80C3h The operating sources (memory) of the CPU are temporarily
occupied.
0 0 1 80C4h Communication error (occurs temporarily; a repetition in the
user application is reasonable).
0 0 1 80D2h Module start address is wrong.
At a reboot of the CP, the output parameters are set as follows:
n DONE = 0
n NDR = 0
n ERROR = 0
n STATUS = 8180h (at AG_RECV)
n STATUS = 8181h (at AG_SEND)
8.2.4 FC 10 - AG_CNTRL - Control CP 343
The connections of the Ethernet CP 343 may be diagnosed and initialized by means of
the VIPA FC 10.
The following jobs may be executed by parameterizable commands:
n Reading connection information
n Resetting configured connections
The commands of this block are permitted only for SEND/RECV connections based on
the ISO/RFC/TCP and UDP protocols.
Please note that this block calls the FC or SFC 196 AG_CNTRL inter-
nally. These must not be overwritten! The direct call of an internal block
leads to errors in the corresponding instance DB!
The following diagram shows a typical sequence of AG_CNTRL. Here it is shown how the
connection status is initially queried and then, in a second job, how the connection termi-
nation is triggered with the rest command.
Status parameter at reboot
Description
FC 10 in the user program
VIPA SPEED7
Network Communication
Ethernet Communication > FC 10 - AG_CNTRL - Control CP 343