7.3 Access Control
7.3.1 FB 48 - ACONTROL - Access control
With this block a access control can be implemented. After getting a code from an
external keypad, panel or RFID reader, the code is compared with a list. Depending on
the result, then the relative outputs are controlled.
n The access codes are to be applied in a data block, which is specified by ACLBlock.
Here you can also specify which outputs Access1...6 are to be controlled and how
(pulse/static) are they controlled. With the data block up to 16 access codes can be
treaded.
n Via AccessCode1...4 the code of the corresponding input device is specified.
n Via CheckCode1...4 the code is compared with the code in your data block ACLBlock.
If the access code in the data block exists, the corresponding outputs are con-
trolled according to the specifications. With configured pulse output you can
specify the pulse duration with TimePulse.
If the access code does not exist in the data block, the output Error is set for the
duration TimeError.
n With an edge change 0-1 of CentralLock all the access codes are disabled. Here the
output CentralLocked is set.
n With an edge change 0-1 of CentralUnlock all the access codes are enabled and the
output CentralLocked is reset.
Parameter Declaration Data type Description
AccessCode1 INPUT STRING[16] Access code, e.g. from keypad.
CheckCode1 INPUT BOOL With an edge change 0-1, the AccessCode1 is
compared with the access code in the data block
ACLBlock.
Default: 0
AccessCode2 INPUT STRING[16] Access code, e.g. from panel.
CheckCode2 INPUT BOOL With an edge change 0-1, the AccessCode2 is
compared with the access code in the data block
ACLBlock.
Default: 0
AccessCode3 INPUT STRING[16] Access code, e.g. RFID reader.
CheckCode3 INPUT BOOL With an edge change 0-1, the AccessCode3 is
compared with the access code in the data block
ACLBlock.
Default: 0
AccessCode4 INPUT STRING[16] Access code, e.g. from an other system
CheckCode4 INPUT BOOL With an edge change 0-1, the AccessCode4 is
compared with the access code in the data block
ACLBlock.
Default: 0
CentralLock INPUT BOOL With an edge change 0-1 all the access codes are
disabled. Here the output CentralLocked is set.
CentralUnlock INPUT BOOL With an edge change 0-1 of CentralUnlock all the
access codes are enabled and the output Central-
Locked is reset.
Description
Parameters
VIPA SPEED7
Building Control
Access Control > FB 48 - ACONTROL - Access control