7.3 Access Control
7.3.1 FB 48 - ACONTROL - Access control
With this block a access control can be implemented. After getting a code from an
external keypad, panel or RFID reader, the code is compared with a list. Depending on
the result, then the relative outputs are controlled.
n The access codes are to be applied in a data block, which is specified by ACLBlock.
Here you can also specify which outputs Access1...6 are to be controlled and how
(pulse/static) are they controlled. With the data block up to 16 access codes can be
treaded.
n Via AccessCode1...4 the code of the corresponding input device is specified.
n Via CheckCode1...4 the code is compared with the code in your data block ACLBlock.
– If the access code in the data block exists, the corresponding outputs are con-
trolled according to the specifications. With configured pulse output you can
specify the pulse duration with TimePulse.
– If the access code does not exist in the data block, the output Error is set for the
duration TimeError.
n With an edge change 0-1 of CentralLock all the access codes are disabled. Here the
output CentralLocked is set.
n With an edge change 0-1 of CentralUnlock all the access codes are enabled and the
output CentralLocked is reset.
Parameter Declaration Data type Description
AccessCode1 INPUT STRING[16] Access code, e.g. from keypad.
CheckCode1 INPUT BOOL With an edge change 0-1, the AccessCode1 is
compared with the access code in the data block
ACLBlock.
Default: 0
AccessCode2 INPUT STRING[16] Access code, e.g. from panel.
CheckCode2 INPUT BOOL With an edge change 0-1, the AccessCode2 is
compared with the access code in the data block
ACLBlock.
Default: 0
AccessCode3 INPUT STRING[16] Access code, e.g. RFID reader.
CheckCode3 INPUT BOOL With an edge change 0-1, the AccessCode3 is
compared with the access code in the data block
ACLBlock.
Default: 0
AccessCode4 INPUT STRING[16] Access code, e.g. from an other system
CheckCode4 INPUT BOOL With an edge change 0-1, the AccessCode4 is
compared with the access code in the data block
ACLBlock.
Default: 0
CentralLock INPUT BOOL With an edge change 0-1 all the access codes are
disabled. Here the output CentralLocked is set.
CentralUnlock INPUT BOOL With an edge change 0-1 of CentralUnlock all the
access codes are enabled and the output Central-
Locked is reset.
Description
Parameters
VIPA SPEED7
Building Control
Access Control > FB 48 - ACONTROL - Access control