YASKAWA VIPA SPEED7 - SFB 31 - NOTIFY_8 P - Messages Without Acknowledge Display (8 X)

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ERROR STATUS
(decimal)
Description
1 4 Error in transmission range pointers SD_i with respect to
the length or the data type
1 8 Partner CPU access error
1 10 Access to local application memory not possible (e.g.
access to deleted DB).
1 12 The call to the FB/SFB
contains an instance DB that does not belong to the
FB/SFB 15.
contains a global DB instead of an instance DB.
could not locate an instance DB (load a new instance DB
from the PG).
1 20 Not enough memory.
n Siemens S7-300 Communication
In order to ensure data consistency, send area SD_1 may not be used again for
writing until the current send process has been completed. This is the case when
the state parameter DONE has the value "1".
n Siemens S7-400 Communication
When a send operation is activated (rising edge at REQ) the data to be sent from
the send area SD_i are copied from the user program. After the block call, you
can write to these areas without corrupting the current send data.
14.2.11 SFB 31 - NOTIFY_8P - Messages without acknowledge display (8x)
Generating block related messages without acknowledgement display for 8 signals.
n SFB 31 NOTIFY_8P represents an extension of SFB 36 "NOTIFY" to 8 signals.
n A message is generated if at least one signal transition has been detected. A mes-
sage is always generated at the initial call of SFB 31. All 8 signal are allocated a
common message number that is split into 8 sub-messages on the displaying device.
n One memory with 2 memory blocks is available for each instance of SFB 31
NOTIFY_8P.
n The displaying device shows the last two signal transitions, irrespective of message
loss.
Before you call SFB 31 NOTIFY_8P in a automation system, you must
insure that all connected displaying devices know this block. More infor-
mation about this may be found in the manuals of the components used.
Data consistency
Description
Parameter
VIPA SPEED7
Integrated Standard
System Function Blocks > SFB 31 - NOTIFY_8P - Messages without acknowledge display (8x)
HB00 | OPL_SP7 | Operation list | en | 18-30 746