3.20 Timer instructions
Starting or resetting a timer (addressed directly or via parameters).
The time value must be in ACCU1-L.
Com-
mand
Operand Parameter Function Length
in words
SP T f 0 ... 511 Start time as pulse on edge change from "0" to "1" 1/2
Timer para. 2
SE T f 0 ... 511 Start timer as extended pulse on edge change from "0"
to"1"
1/2
Timer para. 2
SD T f 0 ... 511 Start timer as ON delay on edge change from "0" to "1" 1/2
Timer para. 2
SS T f 0 ... 511 Start timer as saving start delay on edge change from
"0" to "1"
1/2
Timer para. 2
SA T f 0 ... 511 Start timer as OFF delay on edge change from "1" to "0" 1/2
Timer para. 2
FR T f 0 ... 511 Enable timer for restarting on edge change from "0" to
"1" (reset edge bit memory for starting timer)
1/2
Timer para. 2
R T f 0 ... 511 Reset timer 1/2
Timer para. 2
Status word BR CC1 CC0 OV OS OR STA RLO /FC
Instruction depends on - - - - - - -
ü
-
Instruction influences - - - - - 0 - - 0
VIPA SPEED7
IL operations
Timer instructions