EasyManua.ls Logo

YASKAWA VIPA SPEED7 - Stations Status Information (DPM, PROFINET-IO, Ethercat) - SSL-ID Xy94 H

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17.18 Stations status information (DPM, PROFINET-IO, EtherCAT) - SSL-ID: xy94h
If you read this partial list, you obtain information about the expected and the current
hardware configuration of centrally installed stations of a DP master system / PROFINET
IO controller system or EtherCAT master system.
Content Value Description
SSL_ID 0094h Expected status of the central stations of a PROFINET-IO control system / PN IO sub-
system-ID
With EtherCAT only the stations configured as mandatory are registered.
n Status bit = 1:
Rack/station configure
0194h Activation status of a station of an IO controller system, which is configured and disa-
bled.
n Status bit = 1
0294h Actual state of the rack in the central configuration of the stations of an IO controller
system
n Status bit = 1:
Rack/station exists, activated and not failed
0694h Diagnostic status of the expansion racks in the central configuration of the stations of a
PROFINET-IO control system / PN IO subsystem-ID
n Status bit = 1:
at least one module of rack/station has malfunction or is de-activated: coming
diagnostics interrupt, neighbourhood interrupt, remove/fit interrupt, failure manda-
tory station
0794h Diagnostic / Maintenance condition of the central stations of a PROFINET-IO control
system / PN IO subsystem-ID
n Status bit = 0:
no problem and no maintenance necessary
n status bit = 1:
rack/station has a problem or maintenance requirement or maintenance request
0994h Set point - actual value difference
n Status bit = 1:
Set point - actual value difference in station exists ModDiffBlock, EC state
unequal master state
0A94h Set point state of the stations of an EtherCAT IO controller system.
In this partial list besides the mandatory stations additionally the optional configured sta-
tions are registered.
n Status bit = 1:
Rack/station configured
0F94h SSL partial list header information
INDEX xxxxh
n 0: Central module
n 1 ... 31: Distributed module at PROFIBUS DP
n 100 ... 115: Distributed module at PROFINET-IO / EtherCAT-IO
Description
Header
VIPA SPEED7
SSL System status list
Stations status information (DPM, PROFINET-IO, EtherCAT) - SSL-ID: xy94h
HB00 | OPL_SP7 | Operation list | en | 18-30 982