Content Value Description
LENTHDR 0102h One record set is 129words long (258bytes).
N_DR xxxxh Number of record sets
Record set SSL_ID: xy94h
INDEX
offset
Content Length Description
0 INDEX 1word
n 0: Central module
n 1 ... 31: Distributed module at PROFIBUS DP
n 100 ... 115: Distributed module at PROFINET-IO / EtherCAT-IO
2 status_0 BOOL
n Group information:
1: one of the following status bits has the value 1
0: all subsequent status bits have the value 0
... status_1 BOOL Status station 1
status_2 BOOL Status station 2
... ...
status_2047 BOOL Status station 2047
A status bit of non-configured racks/stations/devices has the value 0.
Compared to SSL_ID xy92h, the data have been shifted by one bit since
bit status_0 is used for group information.
A virtual PN device on the PROFINET network is configured for the
SLIO CPU of a local SLIO bus. The corresponding SSL_ID xy94h is
filled with this configured station number.
If no virtual PN Device for the SLIO bus is configured, then natively
for the station number 2047 is used.
A virtual PN device is configured on the PROFINET network for the
EtherCAT network. The corresponding SSL xy94h is filled with this
configured station number.
The EtherCAT master (controller) has normally the station number 0.
This can not be located in the SSL xy94h because the bit 0 is used as
a group bit. Thus is set in Topology Mismatch in the SSL xy94h the bit
for the station 512 (maximum station number for EtherCAT).
Important difference to
SSL_ID xy92h
Local SLIO bus
EtherCAT bus
VIPA SPEED7
SSL System status list
Stations status information (DPM, PROFINET-IO, EtherCAT) - SSL-ID: xy94h