Parameter Declaration Data type Description
Duration INPUT TIME Time for the duration the Output is deactivated
respectively PulseOff is activated.
With 0ms the automatic switch off is deactivated.
Default: 0ms
Output OUTPUT BOOL Static output to drive a monostable relay.
PulseOn OUTPUT BOOL Pulse output to control the bistable relay (On
signal).
PulseOff OUTPUT BOOL Pulse output to control the bistable relay (Off
signal).
TimeDebounce CONSTANT TIME Time for debounce of the inputs.
Default: 100ms
TimePulse CONSTANT TIME Time for the pulse duration of PulseOn respec-
tively PulseOff.
Default: 100ms
TimePause CONSTANT TIME Time for the break between resetting and setting
of PulseOn respectively PulseOff.
Default: 100ms
7.2.2 FB 46 - BLIND - Controlling blind
With this block a motorized blind can be controlled. For this you have to release the drive
with Enable.
n The controlling for “lifting” BlindUp and “sinking" BlindDown happens by 2 buttons
(Up/Down respectively CentralUp/CentralDown).
CentralUp/CentralDown: Used for central control of all blinds in a building.
Up/Down: Used for local control of a blind. Here a pending CentralUp/Central-
Down signal is ignored.
n If the corresponding button is pressed longer as the specified TimeShortLong the
blend drive moves to the respective end position. By pressing on of the two buttons
(Up/Down respectively CentralUp/CentralDown) you can stop the movement and
reverse, it if necessary.
n With TimeMaxDuration you can specify the maximum run time of the motor and with
TimePause you can specify the pause for the change of direction.
n By jogging the blend drive shortly moves. With this function you can adjust the blind
slats fine.
n With TimeDebounce you can specify a debounce time for the input signals.
n With Status you can check the position of the blend.
0: Upper limit position
50: Unknown position between the two limit positions
100: Lowest limit position
CAUTION!
The blend drive must have its own limit switches that turn off power auto-
matically!
Description
VIPA SPEED7
Building Control
Room > FB 46 - BLIND - Controlling blind
HB00 | OPL_SP7 | Operation list | en | 18-30 104