Parameters
Parameter Declaration Data type Description
Up INPUT BOOL With an edge change 0-1 the output BlindUp is
activated. Depending on the input signal the blend
drives to the upper limit position or is shortly
moved.
As long as the signal is pending the signals Cen-
tralUp/CentralDown are ignored.
Default: FALSE
Down INPUT BOOL With an edge change 0-1 the output BlindDown is
activated. Depending on the input signal the blend
drives to the lower limit position or is shortly
moved.
As long as the signal is pending the signals Cen-
tralUp/CentralDown are ignored.
Default: FALSE
CentralUp INPUT BOOL With an edge change 0-1 the output BlindUp is
activated. Here the blind moves to the upper limit
position.
Default: FALSE
CentralDown INPUT BOOL With an edge change 0-1 the output BlindDown is
activated. Here the blind moves to the lowest limit
position.
Default: FALSE
TimeMaxDuration INPUT TIME Maximum drive time to reach the respective end
position.
Default: 30s
TimePause INPUT TIME Break between a direction change.
Default: 2s
TimeShortLong INPUT TIME Time for the distinction between jog mode and
continuous mode.
Default: 1s
Enable INPUT BOOL Release for the drive (static)
Default: TRUE
BlindUp OUTPUT BOOL Static output blind “lifting”
BlindDown OUTPUT BOOL Static output blind “sinking”
Status OUTPUT INT
n Status - Blind position
– 0: Upper limit position
– 50: Unknown position between the two
limit positions
– 100: Lowest limit position
TimeDebounce CONSTANT TIME Time for debounce of the inputs.
Default: 100ms
VIPA SPEED7
Building Control
Room > FB 46 - BLIND - Controlling blind
HB00 | OPL_SP7 | Operation list | en | 18-30 105