Status word for: S, R, = BR CC1 CC0 OV OS OR STA RLO /FC
Instruction depends on - - - - - - -
ü
-
Instruction influences - - - - - 0
ü
- 0
The following instructions have a directly effect on the RLO.
Com-
mand
Operand Parameter Function Length
in words
CLR Set RLO to "0" 1
SET Set RLO to "1" 1
NOT Negate RLO 1
SAVE Save RLO into BR-bit 1
Status word for: CLR BR CC1 CC0 OV OS OR STA RLO /FC
Instruction depends on - - - - - - - - -
Instruction influences - - - - - 0 0 0 0
Status word for: SET BR CC1 CC0 OV OS OR STA RLO /FC
Instruction depends on - - - - - - - - -
Instruction influences - - - - - 0 1 1 0
Status word for: NOT BR CC1 CC0 OV OS OR STA RLO /FC
Instruction depends on - - - - -
ü
-
ü
-
Instruction influences - - - - - - 1
ü
-
Status word for: SAVE BR CC1 CC0 OV OS OR STA RLO /FC
Instruction depends on - - - - - - -
ü
-
Instruction influences
ü
- - - - - - - -
3.14 Jump instructions
The jump label is a symbolic jump address with max. 4 characters. These 4 characters
can be composed of letters, numbers and the underscore "_", where the 1. character
must be a letter. Upper and lower case are differentiated. The colon ":" after the jump
label identifies the jump label and initiates the instruction part.
Instructions directly
affecting the RLO
Jump label
VIPA SPEED7
IL operations
Jump instructions
HB00 | OPL_SP7 | Operation list | en | 18-30 44