Variable Data type Description
OB83_MDL_ADDR WORD
n Central or distributed PROFIBUS DP:
– Logical base address of the module affected.
If it is a mixed module, it is the smallest log-
ical address used in the module.
– If the I and O addresses in the mixed block
are equal, the logical base address is the
one that receives the event identifier.
n Distributed PROFINET IO:
– Logical base address of the module/
submodule
OB83_RACK_NUM WORD
n If OB83_RESERVED_1 = A0h:
number of submodule/interface submodule (low
byte)
n If OB83_RESERVED_1 = C4h:
– central: rack number
– distributed PROFIBUS DP:
number of DP station (low byte) and DP
master system ID (high byte)
– distributed PROFINET IO:
physical address: identifier bit (bit 15, 1 =
PROFINET IO), IO system ID (bits 11 ... 14)
and device number (bits 0 ... 10)
OB83_MDL_TYPE WORD
n Central or distributed PROFIBUS DP:
Module type of affected module
(x:irrelevant to the user)
– x5xxh: analog module
– x8xxh: function module
– xCxxh: CP
– xFxxh: digital module
– 8340h: Replacement type identifier for input
module
– 9340h: Replacement type identifier for output
module
– A340h: Replacement type identifier for mixed
module (I/O)
– F340h: Replacement type identifier for
uniquely identifiable module (e.g. with
packed addresses)
n Distributed PROFINET IO:
– 8101h: module type of the inserted module is
the same as the module type of the removed
module
– 8102h: module type of the inserted module is
not the same as the module type of the
removed module
OB83_DATE_TIME DATE_AND_TIME DATE_AND_TIME of day when the OB was called
The following table shows the event that started OB 83:OB83_EV_CLASS
VIPA SPEED7
Organization Blocks
Asynchronous error Interrupts > OB 83 - I/O_FLT2 - Insert / Remove Module
HB00 | OPL_SP7 | Operation list | en | 18-30 91