Status information
ERROR STATUS Description
0 0000h Send job completed without error.
0 7000h First call with REQ = 0, sending not initiated.
0 7001h First call with REQ = 1, sending initiated.
0 7002h Follow-on call (REQ irrelevant ), job being processed
Note: during this processing the operating system accesses the data in the DATA
send buffer.
1 8085h LEN parameter has the value 0 or is greater than the largest permitted value.
1 8086h The ID parameter is not in the permitted address range.
0 8088h LEN parameter is larger than the memory area specified in DATA.
1 80A1h Communications error:
n FB 65 TCON was not yet called for the specified ID
n The specified connection is currently being terminated. Transmission over this
connection is not possible.
n The interface is being reinitialized.
1 80B3h The parameter for the connection type (connection_type parameter in the connection
description) is set to UDP.
Please use the FB 67 TUSEND.
1 80C3h The resources (memory) of the CPU are temporarily occupied.
1 80C4h Temporary communications error:
n The connection to the communications partner cannot be established at this time.
n The interface is receiving new parameters.
1 8822h DATA parameter: Source area invalid: area does not exist in DB.
1 8824h DATA parameter: Range error in ANY pointer.
1 8832h DATA parameter: DB number too large.
1 883Ah DATA parameter: Access to send buffer not possible
(e.g. due to deleted DB).
1 887Fh DATA parameter: Internal error, such as an invalid ANY reference.
1 8F7Fh Internal Error (VIPA specific)
1 8xyyh
General error information
Ä
Chap. 4.2 ‘General and Specific Error Information
RET_VAL’ page 66
VIPA SPEED7
Network Communication
Open Communication > FB 63 - TSEND - Sending data - TCP native and ISO on TCP
HB00 | OPL_SP7 | Operation list | en | 18-30 117