Parameter Declaration Data type Memory block Description
ERROR OUTPUT BOOL I, Q, M, D, L Status parameter ERROR:
n ERROR = 0 + STATUS = 0000h
No warnings or errors.
n ERROR = 0 + STATUS unequal to 0000h
A Warning has occurred. STATUS contains
detailed information.
n ERROR = 1
An error has occurred.
STATUS OUTPUT WORD I, Q, M, D, L Status parameter STATUS, returns detailed infor-
mation about the type of error.
ADDR_1 IN_OUT ANY e.g. I, Q, M, D Pointer indicating the buffers in the partner CPU
into which data is written
ADDR_2 IN_OUT ANY e.g. I, Q, M, D Pointer indicating the buffers in the partner CPU
into which data is written
ADDR_3 IN_OUT ANY e.g. I, Q, M, D Pointer indicating the buffers in the partner CPU
into which data is written
ADDR_4 IN_OUT ANY e.g. I, Q, M, D Pointer indicating the buffers in the partner CPU
into which data is written
SD_i,1≤I ≤4 IN_OUT ANY I, Q, M, D, T, C Pointer to the data buffers in the local CPU that
contains the data that must be sent. Only data type
BOOL is valid (Bit field not permitted), BYTE,
CHAR, WORD, INT, DWORD, DINT, REAL, DATE,
TOD, TIME, S5TIME, DATE_AND_TIME,
COUNTER, TIMER.
n The partner CPU stores the data at the respective address and returns an acknowl-
edgment.
n This acknowledgment is tested and when an error is detected in the data transfer
parameter DONE is set to 1 with the next call of FB/SFB 15.
n The write process can only be activated again when the most recent write process
has been completed. The amount, length and data type of the buffer areas that were
defined by means of parameters ADDR_i and SD_i, 1 ≤ I ≤ 4 must be identical.
ERROR STATUS
(decimal)
Description
0 11 Warning: the new task is not active since the previous
task has not completed.
0 25 The communication process was initiated. The task is
being processed.
1 1 Communication failures, e.g.
n Connection parameters not loaded
(local or remote)
n Connection interrupted
(e.g.: cable, CPU turned off, CP in STOP)
1 2 Negative acknowledgment from partner device. The func-
tion cannot be executed.
Function
Error information
VIPA SPEED7
Network Communication
Ethernet Communication > FB/SFB 15 - PUT - Remote CPU write
HB00 | OPL_SP7 | Operation list | en | 18-30 166