Name Declara-
tion
Type Description
EXCEPTION_COUNT STAT WORD Counter for each negatively acknowledged Modbus
request.
SUCCESS_COUNT STAT WORD Counter for each positively acknowledged Modbus
request.
BAD_CRC_COUNT STAT WORD Counter for each valid Modbus request with CRC
error.
FC1_ADDR_OUTPUT_START STAT WORD Modbus Function code 01h start register for Q0.0
Default: 0
FC1_ADDR_OUTPUT_END STAT WORD Modbus Function code 01h end register for Qx.y
Default: 19999
FC1_ADDR_MEMORY_START STAT WORD Modbus Function code 01h start register for M0.0
Default: 20000
FC1_ADDR_MEMORY_END STAT WORD Modbus Function code 01h end register for Mx.y
Default: 39999
FC2_ADDR_INPUT_START STAT WORD Modbus Function code 02h start register for I0.0
Default: 0
FC2_ADDR_INPUT_END STAT WORD Modbus Function code 02h end register for Ix.y
Default: 19999
FC2_ADDR_MEMORY_START STAT WORD Modbus Function code 02h start register for M0.0
Default: 20000
FC2_ADDR_MEMORY_END STAT WORD Modbus Function code 02h end register for Mx.y
Default: 39999
FC4_ADDR_INPUT_START STAT WORD Modbus Function code 04h start register for IW0
Default: 0
FC4_ADDR_INPUT_END STAT WORD Modbus Function code 04h end register for IWx
Default: 19999
FC4_ADDR_MEMORY_START STAT WORD Modbus Function code 04h start register for MW0
Default: 20000
FC4_ADDR_MEMORY_END STAT WORD Modbus function-Code 04 h end register for MW0
Default: 39999
FC5_ADDR_OUTPUT_START STAT WORD Modbus Function code 05h start register for Q0.0
Default: 0
FC5_ADDR_OUTPUT_END STAT WORD Modbus Function code 05h end register for Qx.y
Default: 19999
FC5_ADDR_MEMORY_START STAT WORD Modbus Function code 05h start register for M0.0
Default: 20000
FC5_ADDR_MEMORY_END STAT WORD Modbus Function code 05h end register for Mx.y
Default: 39999
VIPA SPEED7
Modbus Communication
RTU > FB 73 - RTU_MB_SLAVE - Modbus RTU slave
HB00 | OPL_SP7 | Operation list | en | 18-30 194