1: 1bit 2: 1.5bit* 3: 2bit
*) Only permitted when CHARLEN = 0 (5bit)
The parameter FLOWCONTROL is ignored. When sending RTS=1, when receiving
RTS=0.
Special function in System MICRO CPU
From firmware version 2.4.4 with a System MICRO CPU you can switch
between RS422 and RS485 communication.
0: RS422 communication
1: RS485 communication
Return values send by the block:
Error code Description
0000h no error
809Ah Interface not found e. g. interface is used by PROFIBUS
8x24h Error at FC/SFC-Parameter x, with x:
1: Error at PROTOCOL
2: Error at PARAMETER
3: Error at BAUDRATE
4: Error at CHARLENGTH
5: Error at PARITY
6: Error at STOPBITS
7: Error at FLOWCONTROL
809xh Error in FC/SFC parameter value x, where x:
1: Error at PROTOCOL
3: Error at BAUDRATE
4: Error at CHARLENGTH
5: Error at PARITY
6: Error at STOPBITS
7: Error at FLOWCONTROL (parameter is missing)
8092h Access error in parameter DB (DB too short)
828xh Error in parameter x of DB parameter, where x:
1: Error 1. parameter
2: Error 2. parameter
...
FLOWCONTROL
RETVAL FC/SFC 216
(Return values)
VIPA SPEED7
Serial Communication
Serial communication > FC/SFC 216 - SER_CFG - Parametrization PtP
HB00 | OPL_SP7 | Operation list | en | 18-30 207